AUGUST 4, 2026
Live Feed
Back to database
Case File

CVE-2022-30314

MEDIUM · CVSS 4.6 EPSS 0.29%

Source: NVD + CISA KEV + EPSS (historical backfill) · Published 2022-07-28 · Last synced 2026-08-04

CyberRota Analysis

AI analysis pending.

CVE
CVE-2022-30314
Severity
MEDIUM
CVSS
4.6
EPSS
0.29%

Original NVD Description

Honeywell Experion PKS Safety Manager 5.02 uses Hard-coded Credentials. According to FSCT-2022-0052, there is a Honeywell Experion PKS Safety Manager hardcoded credentials issue. The affected components are characterized as: POLO bootloader. The potential impact is: Manipulate firmware. The Honeywell Experion PKS Safety Manager utilizes the DCOM-232/485 serial interface for firmware management purposes. When booting, the Safety Manager exposes the Enea POLO bootloader via this interface. Access to the boot configuration is controlled by means of credentials hardcoded in the Safety Manager firmware. The credentials for the bootloader are hardcoded in the firmware. An attacker with access to the serial interface (either through physical access, a compromised EWS or an exposed serial-to-ethernet gateway) can utilize these credentials to control the boot process and manipulate the unauthenticated firmware image (see FSCT-2022-0054).